QA

Question: Why Does My Furnace Keep Turning On And Off

When a furnace keeps turning on and off, it is usually due to short cycling. This is the term used to describe problems originating from within the heating system. If short cycling is not promptly diagnosed and corrected, it could cause permanent damage to your heating unit and higher utility bills.

How do I stop my furnace from short cycling?

Dirty Flame Sensor Once the sensor becomes contaminated with dirt, it will be unable to detect the presence of flames and will shut the furnace off. The easiest way to fix a furnace that is short cycling is to remove the flame sensor to clean it. Use a sponge or brush to remove the dirt from the sensor.

Why does my furnace turn on and off every few minutes?

When a furnace starts and shuts off, it could be a sign that you have low airflow. The heat exchanger in the furnace will often overheat if there isn’t enough airflow. The furnace won’t be able to pull fresh air into the blower if the air filters are clogged with dust, pet hair, and other debris.

Can a bad thermostat cause a furnace to short cycle?

A faulty thermostat can be a possible culprit for short cycling. If you’re experiencing a furnace short cycling, the first and easy thing you can do is check your thermostat to see if it’s performing correctly. Many times, a homeowner may forget to switch their thermostat over to the heating mode.

Why does my furnace keep shutting off after a few seconds?

A common reason a furnace short cycles is because the heat exchanger, the part that heats your air, is getting too hot due to a lack of airflow. Once the heat exchanger overheats, it trips the high limit switch, which shuts the furnace down to protect it.

How do you know a thermostat is bad?

7 Signs You Need to Replace Your Thermostat Your HVAC Keeps Turning On or Off. Faulty Thermostat Readings. Suspiciously High Energy Bills. Constant Temperature Shifts. Thermostat Is Too Old. Thermostat Fails to Respond to Changed Settings. Your HVAC System Short Cycles.

How often should a furnace cycle on and off?

On average, furnaces should kick on and off anywhere from 3-8 times per hour. However, if your furnace does so more frequently, don’t assume it’s short cycling just yet.

Why does my furnace turns off before reaching temperature?

A lack of airflow can cause your furnace to stop heating before reaching the set temperature. Ensure there is nothing impeding airflow around your furnace, within your furnace and through your ducts. Inside your furnace should be clean and free of debris, especially around the blower motor and the heat exchanger.

Why won’t my furnace shut off?

If your furnace won’t turn off, the easiest issue to fix is your thermostat. A furnace that is working hard to keep a high temperature, especially when it’s extra cold outside, can seem to run continuously. The second common thermostat problem is the fan switch. Your fan can be adjusted manually from your thermostat.

Why does my furnace keep running?

A dirty furnace filter is the number one reason we’ve found that furnaces run constantly. The air filter captures dust, pet hair, and debris that could damage the furnace and keeps it from getting to the heat exchanger. If the filter is dirty, it restricts airflow across the heat exchanger, which causes it to overheat!Nov 24, 2015.

How long should furnace run before shutting off?

Running 10 to 15 minutes per cycle seems acceptable. So is running as long as 20 minutes. Even running every seven or eight minutes may not be a problem, as other factors could lead to more frequent cycling.

Is short cycling an emergency?

Yes. Short cycling is problematic. It may be an indicator that something is wrong with your heating system. In situations where your furnace, heat pump, or ductless system is running incredibly short cycles, you should bring in an experienced HVAC technician to diagnose the issue.

Can you run a furnace without a filter?

Technically, you can temporarily run a furnace without a filter. The consequences of running a furnace without a filter include: Poor air quality: For one, not having a filter in place means there is nothing to prevent dust and debris from being sucked into your furnace and recirculated throughout your home.

How do I test my furnace thermostat?

How to Test Your Furnace Thermostat Step 1: Reset the thermostat lower or higher. Step 2: Make sure the thermostat is ON. Step 3: Check the wiring. Step 4: Turn breaker back on. Step 5: Reexamine wires. Step 6: Wrap wires together.

How do you tell if you need a new thermostat in your house?

Signs You Need a New Thermostat Heating or cooling system will not turn off or on. The temperature reading is incorrect. Recent spike in your energy bill. Frequent temperature fluctuations. Thermostat is 10 years old or older.

How do I stop short cycling?

How To Stop and Prevent Short-Cycling Check your air filter. Believe it or not, a clogged air filter can cause a wide variety of air conditioning issues. Check your thermostat placement. Check your air conditioner’s refrigerant levels. Replace the low-pressure control switch. Check the compressor.

How do I know if my furnace is short cycling?

If your furnace turns on and off repeatedly for short bursts of time, not allowing the house to reach its proper temperature, it is short-cycling. In other words, the heating cycle and the resting cycle are each too short for the furnace to accomplish anything.