Table of Contents
Aux heat will kick on when your heat pump cannot deliver enough warmth to heat your home. Typically, your heat pump will energize the auxiliary heat strip inside your secondary heating source to help reach its set temperature faster.
How do I stop my auxiliary heat from coming on?
Tips for Avoiding AUX Heat Issues Schedule preventative maintenance every six months. Clean the areas around the outdoor HVAC unit regularly. Keep ducts and heat vents free of clutter. Don’t use the emergency heating setting for normal heating. Clean or replace the heat pump filter every month or two.
Why does my heat keep switching to auxiliary heat?
Most heat pumps are designed to automatically switch to AUX heat when the indoor temperature is 3 degrees colder than the thermostat setting. So first, check to see if your thermostat only says AUX when you raise the thermostat 3 degrees or higher than the current temperature of your home. If so, that’s normal.
Is auxiliary heat supposed to come on?
To recap, auxiliary, or emergency heat should only be on when the outside temperature is below freezing. Down here in the south, that should mostly happen at night and during the occasional snowstorm. However, if the weather is warmer and above the freezing level, your auxiliary heat should automatically turn off.
Why does my heat pump stay on auxiliary heat?
Why Is My Heat Pump Auxiliary Heat Always On? Typically, your heat pump will tag in auxiliary heat when outdoor temps drop below 35°F, your heat pump is set to the defrost setting, or you’re attempting to heat your home by 3°F or more at a time. If it is, turn off this setting and check if this disables the aux heat.
How often should AUX heat come on?
When should my auxiliary heat come on? When outside temperatures drop below 40 degrees. While undergoing the defrost cycle. When there is a 3 degree difference or more in the current temperature in your home and the thermostat setting.
Is AUX heat bad?
Is AUX heat bad? The short answer is no. In fact, aux heat is a critical mechanism that keeps your heat pump properly running when the outdoor temperature drops. Since this type of unit doesn’t work the same as a furnace, it can get cold.
Why is my heat not shutting off?
One of the most common issues is the thermostat. The wiring, switches, or heating sensors can fail on your unit. A faulty check valve could be the cause of this type of heating system to fail. If your heating system will not shut down, then you need to call a professional technician for help.
At what temperature should you switch a heat pump to emergency heat?
The Emergency Heat or Auxiliary Heat setting is the second stage of your heating system that is used when the temperature is too low for the heat pump to be able to remove heat from outside, typically below 35 degrees Fahrenheit.
Why is my heat pump blowing cold air?
If it gets too cold outside, your heat pump’s outdoor unit may freeze, causing your system to go into defrost mode. If your heat pump is blowing cold air, look outside and see if your outdoor unit is frozen or has frost on it. If so, your heat pump is likely in defrost mode and you don’t need to call a technician.
Should my heat pump run when auxiliary heat is on?
You should only use your heat pump’s emergency heating mode when it’s truly an emergency (e.g., your heat pump isn’t working in winter) because manually overriding your system means it won’t run as efficiently as it can—which will result in higher energy bills.
How do I know if my auxiliary heat is working?
Just feed the electronic probe into the supply outlet. If the heat pump is off you will know it. You cannot heat a house with 55 degree air.
How long can aux heat stay on?
By default, this time is set to five minutes. This means, if your aux heat is called upon and canceled immediately, it will still run for five minutes before shutting down. If you change the threshold settings, you can configure the minimum on time and save on electricity or heating oil.
What is Stage 2 auxiliary heat?
First-stage auxiliary heating for heat pumps and multi-stage furnaces; provides supplemental gas or electric heat when the heat pump cannot meet demand. Stage 2 Aux Heating. Second-stage auxiliary heating for heat pumps and multi-stage furnaces.
How do you know a thermostat is bad?
7 Signs You Need to Replace Your Thermostat Your HVAC Keeps Turning On or Off. Faulty Thermostat Readings. Suspiciously High Energy Bills. Constant Temperature Shifts. Thermostat Is Too Old. Thermostat Fails to Respond to Changed Settings. Your HVAC System Short Cycles.
Is emergency heat and auxiliary heat the same?
Auxiliary heating turns on automatically to help heat your home more quickly if the temperature drops suddenly. The emergency heat setting has to be manually switched on and should only be used in temperatures below 30 degrees.
What is the most common form of auxiliary heat used in heat pumps?
Electric auxiliary heating systems, which are the most common, have coils similar to what’s inside a toaster. These coils help heat the air more quickly. The auxiliary heater is a supplement to the heat pump, not a replacement, and helps the heat pump run more efficiently.