Table of Contents
All you have to do is to multiply the length of your room in feet by the width of your room in feet, and then multiply that by 25. That will give you the BTU needed to properly cool your room. All it takes is a simple multiplication!Oct 16, 2019.
How many BTU do I need for a 12×12 room?
If you want to properly cool down a 300 square foot area (or room), you need a 6,000 BTU air conditioner. Obviously, the problem arises when you have a tiny 12×12 room, for example. According to the US Department of Energy directive, an air conditioner’s most appropriate size would be 2,880 BTU unit.
How do I calculate what size air conditioner I need?
To calculate the size of the air conditioner you need for a room, first, multiply the length of the room with its width. Then multiply it with 25 BTU to get the ample cooling for the room under different weather conditions. For example, if the room is 15 feet long and 12 feet wide, it comes to 180 square feet.
How many sq ft does a 15000 BTU AC cool?
Those in the 12,000- to 15,000-Btu range cost from $450 to $600, while large units go up to $1,200. Air conditioners rated at 15,000 Btu should be enough to cool most rooms up to about 875 sq. ft.
How many BTU do I need to cool a 20×20 room?
Rule of thumb. A 1 ton (12,000 BTUH) unit is doable in the space you want to cool. To handle the hot, humid summer heat of your area, I would increase it to 15,000 – 16,000 BTUH.
What size room will a 12000 BTU air conditioner cool?
A 12000 Btu unit will effectively cool a room with a floor space of 500 to 600 square feet.
What size room will a 10000 BTU air conditioner cool?
10,000 BTUs will cover 300 sq. ft. (2,400 cubic feet) 12,000 BTUs will cover 400 sq.
How many BTUs is 1hp aircon?
When choosing an air conditioner, usually a 1 HP (horse power) equipment is able to remove 9,000 BTU/hr of heat. With better technology, some machines are able to remove 10,000 BTU/hr of heat with the same capacity. The higher the listed BTU/hr, the greater the cooling capacity.
How do you calculate BTU output?
Step 1: Measure The Square Footage (Length, Width, Height Exact To 0.25 Ft) Square Footage = Measured Length x Measured Width. Square Footage = 16 3/4 ft (Length) x 14 1/2 ft (Width) = 243 sq ft. BTU Requirement = 500 sq ft x 20 BTU per sq ft = 10,000 BTU. Accurate BTU Calculation = 20,000 BTU * 1.1 + 600 BTU = 22,600 BTU.
How many sq ft will 18000 BTU cool?
BTU Sizing Chart for Mini Split Systems Area To Be Cooled Capacity Needed (BTUs Per Hour) 450 to 550 square feet 12,000 BTUs 550 to 700 square feet 14,000 BTUs 700 to 1,000 square feet 18,000 BTUs 1,000 to 1,200 square feet 21,000 BTUs.
Is 12000 BTU too much?
The most common window air conditioning units come in cooling capacities ranging from 5,000 to 12,000 Btu. A 12,000 Btu air conditioner can cool between 450 and 550 square feet of floor space. A 12,000 Btu unit could cool a room 25 feet long by 20 feet wide that has 500 square feet of floor area.
How many square feet will 18000 BTU heat?
There are calculators available to help homeowners factor the right sized unit, but there are also some rules of thumb that can be followed. For example, a 300 square foot room typically requires 7,000 BTUs to maintain a comfortable temperature, while a 1,000 square foot room requires 18,000 BTUs.
How many BTUs do I need to cool my house?
Size and Ceiling Height Area To Be Cooled (square feet) Capacity Needed (BTUs per hour) 450 to 550 12,000 550 to 700 14,000 700 to 1,000 18,000 1,000 to 1,200 21,000.
Do they make 7000 BTU air conditioner?
SereneLife12,000 BTU (7,000 BTU, DOE) Portable 4-in-1 Air Conditioner with Heater in White for Rooms Up to 450 sq. ft.
What size air conditioner do I need for a 2400 square foot home?
The answer to the question, “what size AC unit for 2400 square feet?”, would be, is 60,000 BTUs or 5 Tons. It’s possible to fall between unit sizes, so if that’s the case with you, then you should choose the next higher size. That way, you can be sure that the AC unit can still cool a given area sufficiently.
What size air conditioner do I need for 50 square meters?
Small shops and offices also are typically in the 45 to 50-square metre range. In this case, the best capacity is seven to eight kW. For bedrooms, small kitchens, and lounges that are 10 square metres, a 2.6kW air conditioning unit will suit them.
Can window AC cool entire house?
Window air conditioners are designed to cool only a single room. It is very difficult for such AC to cool an entire house. At most you can cool two adjacently connected tiny rooms with a single window AC, but there will be uneven cooling.
Is 8000 BTU enough for living room?
Consumer Reports recommends 20 BTUs per square foot of the living space (or spaces) you want to cool down. 300 – 350 sq. feet: 8,000 BTUs. 350 – 400 sq.
Is the higher the BTU better or worse?
A heater with a higher BTU rating is more powerful — that is, it has a higher heat output — than one with a low BTU rating. It can do more to raise the temperature in your room each hour, so you can either heat a room more quickly or heat a larger space.