Table of Contents
How do you remove an air return grille?
To separate the grille from the metal frame in preparation for installation, follow the 3 steps below: Place your fingers in the center of the grille frame as indicated by the arrow. Allow the lower brackets to clear bottom lip of the metal frame. Slide the grille out at a very slight angle. Remove old metal grille.
Should return vent face up or down?
There is no proper direction for the vanes to point. If they’re high sidewall, normally they would be pointed upward which makes them vision proof and just the opposite for low sidewall.
Where should the return vent be located?
The best location of the return vents depends on whether the system is heating or cooling the air. If it’s cooling, the return vents should be near the ceiling, where the warm air collects, but if it’s heating, the return vents should draw cool air from the floors.
What happens if there is not enough return air?
If there is not enough return air available, your HVAC system will not heat or cool properly. If not enough air is brought back, your HVAC system will not be able to keep up with temperature demands. In some cases, two returns may be necessary to provide enough return air.
Can flexible duct be used for return air?
Flex duct is widely used for return air in commercial air conditioning systems. Flex duct is able to withstand a certain negative pressure of return air. When installed properly, a flex duct is a reliable and convenient ductwork solution. Flex duct often gets a bad rep because of airflow issues.
How much does it cost to add a return vent?
Cost of Return Air Plenums Return Air Plenums Costs Zip Code Basic Best Return Air Plenums – Material Prices $50.00 – $60.00 $95.00 – $105.00 Return Air Plenums – Installation Cost $100.25 – $100.35 $150.00 – $200.00 Return Air Plenums – Total $150.25 – $160.35 $245.00 – $305.00.
How do you size a return grill?
To calculate return air grille size, take the CFM of the HVAC unit and divide it by 350 to get the grille area in square feet. Next, multiply the grille area by 144 to convert it into square inches. Finally, choose your preferred grille size that matches the required grille area.
Can you hang a picture over a return air vent?
Much like the louvered doors, louvered shutters can be used to hide a return air vent without obstructing airflow. These can be hung over the return vent like a picture would be or secured to the wall with hinges allowing you to open and close the shutters when it’s time to replace your return vent filters.
What is the return vent?
What is a Return Air Vent? An air conditioner works by absorbing the warm air and moisture from your home. Once the dampness is separated from the air, your AC unit cools the warm air, and sends it back into your home through the return air vents. So, in a nutshell, it recycles air from each room in your home.
How big should my return air duct be?
The duct for this system must be sized by using 6 square inches of clear duct area for each 1000 BTU of cooling. Each ton of cooling contains 12,000 BTU. Multiply the tonnage, 3.5, by the total BTU per ton and this will give you the total BTU rating.
Do you put a filter in a return vent?
Should you use a filter in your return vent? For most homes, return vents filters are suggested. They typically won’t cause any damage to your HVAC system and are easy to install – there’s no need for an HVAC technician.
Should every room have a return vent?
While it is a myth that air return grilles are required in each and every room in the house, it is definitely necessary to have more than one of these grilles installed at strategic places in the house. Likewise, you can also install these in rooms that have a high footfall or usage in the house.
How many return vents do you need in a house?
Having several return vents (ideally one in every room, but even two or three is better than just one) creates consistent air pressure. If you have one return vent, your home is fine. Keep the doors to each room open so air can properly circulate.
Can there be too much return air?
Can an air return be too big? No, an air return cannot be too big, except in extreme cases where a closed room is temporarily under negative air pressure. Return vents maintain air pressure, filter out debris, and are critical to the efficient operation of any HVAC system.
How do I know if my return air is working?
Try this simple test when your HVAC system is running: get a piece of tissue paper and dangle it about six inches from one of the return vents. You should be able to see it being gently pulled towards the vent. Next, place it up against return vent and see if the air suction holds it in place.