QA

Question: How To Figure Btu For Air Conditioner

All you have to do is to multiply the length of your room in feet by the width of your room in feet, and then multiply that by 25. That will give you the BTU needed to properly cool your room. All it takes is a simple multiplication!Oct 16, 2019.

How many BTU do I need for a 12×12 room?

If you want to properly cool down a 300 square foot area (or room), you need a 6,000 BTU air conditioner. Obviously, the problem arises when you have a tiny 12×12 room, for example. According to the US Department of Energy directive, an air conditioner’s most appropriate size would be 2,880 BTU unit.

How many square feet can a 12000 BTU air conditioner cool?

The size of your space determines how much cooling capacity you need. Budget air conditioners range from 5,000 BTU, which can handle about 150 square feet, to 12,000 BTU, enough to cover about 550 square feet.

How do I calculate what size air conditioner I need?

To calculate the size of the air conditioner you need for a room, first, multiply the length of the room with its width. Then multiply it with 25 BTU to get the ample cooling for the room under different weather conditions. For example, if the room is 15 feet long and 12 feet wide, it comes to 180 square feet.

How many BTU do I need calculator?

For example, a 300 square foot room typically requires 7,000 BTUs to maintain a comfortable temperature, while a 1,000 square foot room requires 18,000 BTUs. A simple formula to determine your heating needs is: (desired temperature change) x (cubic feet of space) x . 133 = BTUs needed per hour.

Is 8000 BTU enough for a bedroom?

Recommended BTU By Room Size If you are looking for an air conditioner for a room measuring say 10′ x 15′ (150 square feet), the recommended BTU range is up to 5400. Once you get into 340 and 400 square feet per room, you’d need an 8,000 or 9,000 BTU air conditioner, respectively.

How many BTU do I need for a 20×20 room?

Rule of thumb. A 1 ton (12,000 BTUH) unit is doable in the space you want to cool. To handle the hot, humid summer heat of your area, I would increase it to 15,000 – 16,000 BTUH.

How many sq ft will 18000 BTU cool?

BTU Sizing Chart for Mini Split Systems Area To Be Cooled Capacity Needed (BTUs Per Hour) 450 to 550 square feet 12,000 BTUs 550 to 700 square feet 14,000 BTUs 700 to 1,000 square feet 18,000 BTUs 1,000 to 1,200 square feet 21,000 BTUs.

How many sq ft does a 15000 BTU AC cool?

Those in the 12,000- to 15,000-Btu range cost from $450 to $600, while large units go up to $1,200. Air conditioners rated at 15,000 Btu should be enough to cool most rooms up to about 875 sq. ft.

What size air conditioner do I need for a 2400 square foot home?

The answer to the question, “what size AC unit for 2400 square feet?”, would be, is 60,000 BTUs or 5 Tons. It’s possible to fall between unit sizes, so if that’s the case with you, then you should choose the next higher size. That way, you can be sure that the AC unit can still cool a given area sufficiently.

What size air conditioner do I need for a 2000 square foot home?

Step 5: Match your square footage to an HVAC size chart Home Sq Footage Air Conditioner Size (tons) 600 – 1,000 square feet 1.5 tons 1,000 – 1,500 square feet 2 tons 1,500 – 2,000 square feet 3 tons 2,000 – 2,500 square feet 4 tons.

How many BTUs is 1hp aircon?

When choosing an air conditioner, usually a 1 HP (horse power) equipment is able to remove 9,000 BTU/hr of heat. With better technology, some machines are able to remove 10,000 BTU/hr of heat with the same capacity. The higher the listed BTU/hr, the greater the cooling capacity.

What size AC do I need for 1200 sq ft?

STEP 1: Determine how many BTUs of heating and tons of AC you need House Square Footage BTUs Needed 500 – 700 14,000 700 – 1,000 18,000 1,000 – 1,200 21,000 1,200 – 1,400 23,000.

Is higher or lower BTU better?

A heater with a higher BTU rating is more powerful — that is, it has a higher heat output — than one with a low BTU rating. It can do more to raise the temperature in your room each hour, so you can either heat a room more quickly or heat a larger space.

Does higher BTU mean more electricity?

The more BTU your unit produces, the more energy it consumes. So, if you are worried about high energy costs, you should get a unit that is appropriate for your space.

What size room will a 10000 BTU air conditioner cool?

10,000 BTUs will cover 300 sq. ft. (2,400 cubic feet) 12,000 BTUs will cover 400 sq.

How many BTU do I need for a 2700 square foot house?

121,500 BTU House Size (Sq Ft): Furnace Size (in BTUs): 2400 sq ft home 108,000 BTU furnace 2500 sq ft home 112,500 BTU furnace 2600 sq ft home 117,000 BTU furnace 2700 sq ft home 121,500 BTU furnace.

Will higher BTU cool faster?

If you’re wondering if an air conditioner with higher BTU’s will cool your room faster, it is possible, but it depends. It also depends on the total cubic feet of the room to be cooled, so if the ceiling height is higher than 10 feet, that is added cubic feet which requires additional cooling power or more BTU’s.

What size air conditioner do I need for a 3000 square foot house?

The recommended capacity for a home that is 1,201 to 1,500 square feet is 2.5 tons. For a home 1,501 to 1,800, the recommended capacity is 3 tons. For a 2,000 square-foot home, the best AC capacity is 3.5 tons. Since larger homes are costlier to cool, you’ll need a 5-ton unit to cool a 3,000 square-foot home.

How many BTU do I need for 700 square feet?

14,000 BTUs Air Conditioning Sizing Chart: 450 to 550 sq ft 12,000 BTUs 550 to 700 sq ft 14,000 BTUs 700 to 1,000 sq ft 18,000 BTUs 1,000 to 1,200 sq ft 21,000 BTUs.

How many BTU is 900 square feet?

A 100- to 200 square-foot room, such as a small home office, will have an average recommendation of 4,000 to 8,000 BTUs. For a space of 800 to 900 square feet, such as a small home or two-bedroom townhouse, the recommendation is between 30,000 and 45,000 BTUs.

What size air conditioner do I need for 50 square meters?

Small shops and offices also are typically in the 45 to 50-square metre range. In this case, the best capacity is seven to eight kW. For bedrooms, small kitchens, and lounges that are 10 square metres, a 2.6kW air conditioning unit will suit them.