Table of Contents
For example, a 300 square foot room typically requires 7,000 BTUs to maintain a comfortable temperature, while a 1,000 square foot room requires 18,000 BTUs. A simple formula to determine your heating needs is: (desired temperature change) x (cubic feet of space) x . 133 = BTUs needed per hour.
How many BTU do I need per square foot?
To determine the number of BTUs per square foot that you need to heat a room, simply multiply the square footage by 20 BTUs per square foot. For example, if a room has 1,000 square feet, you would require 20,000 BTUs to heat it.
How do you calculate BTU for a room?
For each room, multiply the BTU per square footage times the square footage of the room. For example, a home located in Zone 5 with poor insulation would require 60 BTUs per square foot. Therefore, a room that is 300 square feet will need 18,000 BTUs (60 x 300).
How many BTU do I need for a 12×12 room?
6,000 BTU Room Type Room Size Recommended BTU 12 x 12 room 144 sq ft 6,000 BTU 12 x 24 room 576 sq ft 14,000 BTU 13 x 13 room 169 sq ft 6,000 BTU 14 x 16 room 224 sq ft 7,000 BTU.
How do I calculate what size air conditioner I need?
To calculate the size of the air conditioner you need for a room, first, multiply the length of the room with its width. Then multiply it with 25 BTU to get the ample cooling for the room under different weather conditions. For example, if the room is 15 feet long and 12 feet wide, it comes to 180 square feet.
How many BTU is 600 square feet?
Answer: Using the EPA’s 20 BTU per sq ft rule of thumb, the room size of 12,000 BTU air conditioners is 600 sq ft. Equally, 1 ton AC room size is about 600 sq ft. Again, when narrowing down your choice of an air conditioner, knowing how big an area you need to cool is your best friend.
How many BTUs do I need for a 1200 square foot house?
A 1,200-square-foot home will require between 35,000 and 75,000 BTUs. A 1,500-square-foot home will require between 45,000 to 90,000 BTUs.
Is 8000 BTU enough for a bedroom?
Recommended BTU By Room Size If you are looking for an air conditioner for a room measuring say 10′ x 15′ (150 square feet), the recommended BTU range is up to 5400. Once you get into 340 and 400 square feet per room, you’d need an 8,000 or 9,000 BTU air conditioner, respectively.
Is 5000 BTU enough for a bedroom?
According to the EPA’s rule of thumb role, 5000 BTU room size should be 250 sq ft. If you have a 150 sq ft room to cool, 5000 BTU will be more than enough. However, EPA in their rule of thumb specifically recommends that we should calculate: “20 BTU of cooling output per 1 sq ft.”.
How many BTUs is 1hp aircon?
When choosing an air conditioner, usually a 1 HP (horse power) equipment is able to remove 9,000 BTU/hr of heat. With better technology, some machines are able to remove 10,000 BTU/hr of heat with the same capacity. The higher the listed BTU/hr, the greater the cooling capacity.
How many sq ft does a 15000 BTU AC cool?
Those in the 12,000- to 15,000-Btu range cost from $450 to $600, while large units go up to $1,200. Air conditioners rated at 15,000 Btu should be enough to cool most rooms up to about 875 sq. ft.
What size room will 5000 BTU cool?
The size of your space determines how much cooling capacity you need. Budget air conditioners range from 5,000 BTU, which can handle about 150 square feet, to 12,000 BTU, enough to cover about 550 square feet. Naturally, air conditioners with higher capacities have higher price tags.
How many BTU do I need for a 20×20 room?
Rule of thumb. A 1 ton (12,000 BTUH) unit is doable in the space you want to cool. To handle the hot, humid summer heat of your area, I would increase it to 15,000 – 16,000 BTUH.
What size room will a 12000 BTU air conditioner cool?
A 12000 Btu unit will effectively cool a room with a floor space of 500 to 600 square feet.
How many square feet will 40000 BTU heat?
In a standard climate, 40,000 BTU is enough to heat a 1,000 sq ft area. Obviously, if you live in colder climate, a 40,000 BTU heater will heat an area below 1,000 sq ft.
What size air conditioner do I need for a 2400 square foot home?
The answer to the question, “what size AC unit for 2400 square feet?”, would be, is 60,000 BTUs or 5 Tons. It’s possible to fall between unit sizes, so if that’s the case with you, then you should choose the next higher size. That way, you can be sure that the AC unit can still cool a given area sufficiently.
How many BTU do I need for a 2700 square foot house?
121,500 BTU House Size (Sq Ft): Furnace Size (in BTUs): 2400 sq ft home 108,000 BTU furnace 2500 sq ft home 112,500 BTU furnace 2600 sq ft home 117,000 BTU furnace 2700 sq ft home 121,500 BTU furnace.
How many BTUs do I need for 300 square feet?
7,000 BTUs Air Conditioning Sizing Chart: 100 to 150 sq ft 5,000 BTUs 150 to 250 sq ft 6,000 BTUs 250 to 300 sq ft 7,000 BTUs 300 to 350 sq ft 8,000 BTUs.