QA

Quick Answer: How Much Btu Per Square Foot

The Rules for Keeping Cool. Window air conditioners typically have a cooling capacity ranging from 5,000 to 12,500 British thermal units (Btu/hr.). As a rule of thumb, an air conditioner needs 20 Btu for each square foot of living space.

How many BTUs do I need to heat 1500 square feet?

A 1,500-square-foot home will require between 45,000 to 90,000 BTUs.

How many BTU do I need for a 12×12 room?

6,000 BTU Room Type Room Size Recommended BTU 12 x 12 room 144 sq ft 6,000 BTU 12 x 24 room 576 sq ft 14,000 BTU 13 x 13 room 169 sq ft 6,000 BTU 14 x 16 room 224 sq ft 7,000 BTU.

How many BTU do I need for 3500 square feet?

157,500 BTU Home Size (Heating): Standard Climate Very Hot Climate 3,000 square feet 135,000 BTU 90,000 BTU 3,500 square feet 157,500 BTU 105,000 BTU 4,000 square feet 180,000 BTU 120,000 BTU 4,500 square feet 202,500 BTU 135,000 BTU.

How many BTU do I need for a 20×20 room?

Rule of thumb. A 1 ton (12,000 BTUH) unit is doable in the space you want to cool. To handle the hot, humid summer heat of your area, I would increase it to 15,000 – 16,000 BTUH.

How many square feet will a 80000 BTU furnace heat?

How Many Square Feet Will 30,000 – 120,000 BTU Furnace Heat? Furnace Capacity Square Footage(Hot Climate) Square Footage(Cold Climate) 80,000 BTU 2,650 sq ft 1,450 sq ft 90,000 BTU 3,000 sq ft 1,630 sq ft 100,000 BTU 3,320 sq ft 1,810 sq ft 120,000 BTU 4,000 sq ft 2,180 sq ft.

How do I calculate BTU for my house?

For example, a 300 square foot room typically requires 7,000 BTUs to maintain a comfortable temperature, while a 1,000 square foot room requires 18,000 BTUs. A simple formula to determine your heating needs is: (desired temperature change) x (cubic feet of space) x . 133 = BTUs needed per hour.

How many sq ft does a 15000 BTU AC cool?

Those in the 12,000- to 15,000-Btu range cost from $450 to $600, while large units go up to $1,200. Air conditioners rated at 15,000 Btu should be enough to cool most rooms up to about 875 sq. ft.

Is 8000 BTU enough for a bedroom?

Recommended BTU By Room Size If you are looking for an air conditioner for a room measuring say 10′ x 15′ (150 square feet), the recommended BTU range is up to 5400. Once you get into 340 and 400 square feet per room, you’d need an 8,000 or 9,000 BTU air conditioner, respectively.

What size room will 5000 BTU cool?

The size of your space determines how much cooling capacity you need. Budget air conditioners range from 5,000 BTU, which can handle about 150 square feet, to 12,000 BTU, enough to cover about 550 square feet. Naturally, air conditioners with higher capacities have higher price tags.

How many square feet can 18000 BTU cool?

Air Conditioner BTU Chart; With 12,000 BTU (1 Ton) Room Size Example Cooling Capacity (BTU): Room/Area Size: 14,000 BTU air conditioner room size: 600-700 sq ft 16,000 BTU air conditioner room size: 700-800 sq ft 18,000 BTU air conditioner room size: 800-900 sq ft 20,000 BTU air conditioner room size: 900-1,000 sq ft.

What size air conditioner do I need for a 2400 square foot home?

The answer to the question, “what size AC unit for 2400 square feet?”, would be, is 60,000 BTUs or 5 Tons. It’s possible to fall between unit sizes, so if that’s the case with you, then you should choose the next higher size. That way, you can be sure that the AC unit can still cool a given area sufficiently.

How many BTUs do I need for a 1600 sq ft house?

How many btu do I need to heat 3,000 square feet? Room/Area Size Heating Capacity(BTU) 1,400 sq ft 63,000-77,000 BTU 1,500 sq ft 68,000-82,000 BTU 1,600 sq ft 72,000-88,000 BTU 1,700 sq ft 77,000-93,000 BTU.

How many BTU do I need for a 2700 square foot house?

121,500 BTU House Size (Sq Ft): Furnace Size (in BTUs): 2400 sq ft home 108,000 BTU furnace 2500 sq ft home 112,500 BTU furnace 2600 sq ft home 117,000 BTU furnace 2700 sq ft home 121,500 BTU furnace.

What size room will 6000 BTU cool?

You’ll need to know your room size too. In general, a 5,000 to 6,000 BTU air conditioner can cool between 100 and 300 square feet. Seven thousand to 8,200 BTU units are adequate for cooling 250 to 550 square feet, while 9,800 to 12,500 BTU models cool up to 950 square feet.

How many square feet will a 9000 BTU AC cool?

400 square feet Area To Be Cooled Capacity Needed (BTUs Per Hour) 300 to 350 square feet 8,000 BTUs 350 to 400 square feet 9,000 BTUs 400 to 450 square feet 10,000 BTUs 450 to 550 square feet 12,000 BTUs.

Can a furnace be too big for a house?

Oversized furnaces can wreak havoc on your entire HVAC system, indoor air quality, and budget. Furthermore, it is expensive to operate a furnace that is too large. Your monthly energy costs will increase. Also, a system that is too large will require more repairs than one that is properly sized.

Is it better to undersize or oversize a furnace?

Heating systems should never be undersized to prevent discomfort when outdoor temperatures or weather conditions exceed the capacity of the heating source. Although over sizing a heating system can be equally uncomfortable if grossly oversized which can cause large temperature swings and frequent cycling.

How big of a furnace do I need for a 1500 sq ft house?

Generally in a Californian climate you will need 25-30 BTU per square foot. BTU is a measurement of a furnace’s heat output. 1500 sq feet by 25 BTU gives us a 37,500 BTU furnace.