Table of Contents
800 watts Window AC Unit Capacity (in BTU): Power Draw (in Watts): 8,000 BTU 800 watts 9,000 BTU 900 watts 10,000 BTU 1,000 watts 11,000 BTU 1,100 watts.
How many watts does an 8000 BTU air conditioner use?
A mid-size 8,000 BTU AC should use fewer than 715 watts. A big 14,000 BTU air conditioner should only use 1,250 watts.
What size generator will run a 8000 BTU air conditioner?
What Size Generator to Run 5,000 – 15,000 BTU Air Conditioner Air Conditioner Size (BTU) Generator Size (Watts) 6,000 btu 1500 Watts 8,000 btu 1500 Watts 10,000 btu 2000 Watts 12,000 btu 2000 Watts.
How much electricity does a 8000 BTU window AC use?
660 Watts Air Conditioner (BTU) Estimated Watts Small Window AC Unit (5,000 BTU) 550 Watts of electricity Medium Window AC Unit (8,000 BTU) 660 Watts of electricity Large Window AC Unit (15,000 BTU) 1,500 Watts of electricity Small Central Air Conditioner (10,000 BTU) 3,000 Watts of electricity.
How many amps does an 8000 BTU air conditioner use?
Table: How Many Amps Do Window, Portable, Mini-Split Air Conditioners Draw Air Conditioner Capacity Amperage (Estimate) AC Type: How many amps does an 8,000 BTU air conditioner use? 5.80 – 8.70 Amps Window AC, Portable AC How many amps does a 10,000 BTU air conditioner use? 7.25 – 10.87 Amps Window AC, Portable AC.
Can a generator run a 8000 BTU air conditioner?
Expert Reply: An AC unit that is rated for 8,000 BTU draws up to 1,800 watts when starting and 1,200 when running. A 4,000 watt generator like the # 289-AP5000 would easily handle that.
What size inverter do I need to run a 8000 BTU air conditioner?
For a larger AC unit of 8000 BTU’s to as high as 15000 BTU’s you will require a larger power inverter, the 6000 watt dc to ac power inverter should do the trick.
What size room does an 8000 BTU air conditioner cool?
At 8,000 BTU, it has the cooling capacity for up to about 350 square feet.
Will a 2000 watt generator run a 6000 BTU air conditioner?
Most portable generators can handle at least a 6,000 BTU air conditioner, which needs between 500 and 600 watts. You just can’t plug in additional loads that, when added to the requirements of the air conditioner, will exceed the generator’s surge rating.
What size generator do I need to run my AC and refrigerator?
If your power needs are 1600 running watts per hour, you should get a generator with at least 1,800 rated Wattage. If your appliances have a total running wattage of 6800 and a starting wattage of 8200, you should get a generator that can provide 7,500 and 9,500 starting power.
Is 8000 BTU enough for a bedroom?
Recommended BTU By Room Size If you are looking for an air conditioner for a room measuring say 10′ x 15′ (150 square feet), the recommended BTU range is up to 5400. Once you get into 340 and 400 square feet per room, you’d need an 8,000 or 9,000 BTU air conditioner, respectively.
How much electricity does a 8000 BTU air conditioner use per hour?
It will cost you approximately eight cents per hour to run an 8000 BTU air conditioner. If you were to run this unit for eight hours a day for eight months of the year, it would cost you about $150.
How many starting watts does a window AC use?
Typical Window Unit Wattage A typical starting wattage for a window unit is 2200. Once the motor is running steadily, the amperage drops and the wattage usually is around 1500. Your unit may have different ratings. Examine the nameplate or the specifications in the manual to determine how much power your AC unit uses.
How much power does a 9000 BTU air conditioner use?
Power Consumption Of 9,000 BTU Air Conditioners (0.75 Tons/2.6 kW) The power consumption of 9,000 BTU air conditioner units ranges from 800-900 watts (if a 9,000 BTU A/C unit consumes more than 900 watts, it is inefficient and you should look for a better model).
What is the highest BTU air conditioner for 120 volts?
However, the highest BTU air conditioner that can be plugged into a 120-volt outlet is 15,000 BTU. A 15,000 BTU air conditioner can cool up to 750 square feet of space, which is more than enough for the average consumer. This is evidenced by the fact that 8,000 BTU is the most popular AC size for residential use.
How much current does an AC draw?
Central air conditioning requires between 208 and 240 volts to operate and draws between 15 and 60 amps depending on the size.
How big of a generator do I need to power my AC?
If you have a 3-ton (30-Amp, 36,000 BTUs) air conditioner, you need at least a 14 KW generator. If you have a 4-ton (40-Amp, 48,000 BTUs) air conditioner, you need at least a 17 KW generator. If you have a 5-ton (50-Amp, 60,000 BTUs) air conditioner, you need at least a 20 KW generator.
What size generator do I need for a window AC unit?
Portable generators rated from 5,000 to 8,000 watts (W) can generally provide enough power for a window A/C and other necessities.
What size generator do I need to run a portable air conditioner?
Most of the 5000 BTU air conditioners will need a 500 W generator. Something like Jackery 500W generator would be ideal. Jackery 500W is the most popular generator for 5000 BTU air conditioner.