QA

Question: How Many Tons Per Square Foot Hvac

Simple answer: You need 0.0016 tons of AC per square foot. In general, for every 600 sq ft, you need 1 ton of AC. This is a general estimate.

How many sq ft will a 2.5 ton AC cool?

For example, a 30,000 BTU, 2.5-ton air conditioner is made to effectively cool a home between 1,200 and 1,500 square feet. A slightly larger 3,600, 3-ton unit, is designed for homes that are 1,500 to 1,800 square feet.

How many sq ft will a 4 ton AC unit cool?

ZONE 1 ZONE 4 3 Tons 1501 – 1800 sf 1601 – 2000 sf 3.5 Tons 1801 – 2100 sf 2001 – 2250 sf 4 Tons 2101 – 2400 sf 2251 – 2700 sf 5 Tons 2401 – 3000 sf 2751 – 3300 sf.

How big of a house is a 2.5 ton HVAC good for?

According to this common but somewhat inaccurate method, you need 1 ton of air cooling capacity for every so many square feet of living space. While there’s some dispute over the exact amount, an often-used amount is 600 square feet. A 2.5-ton unit, then, theoretically would fit a 1,500-square-foot home.

How many tons of cooling do I need for 2400 square feet?

Therefore, if your home is 2,400 square feet, an AC unit that is between three and four tons would likely be a good choice for cooling your space both effectively and efficiently.

Can you replace a 2 ton AC unit with a 3 ton?

Simple answer: yes. But that really depends on the size of you house and its condition. If the 2 ton unit is working as designed but seems to run continuously without satisfying the thermostat setting, then it might be undersized and replacing it with a 3 ton unit might be the answer.

What size AC do I need for 2000 square feet?

Step 5: Match your square footage to an HVAC size chart Home Sq Footage Air Conditioner Size (tons) 600 – 1,000 square feet 1.5 tons 1,000 – 1,500 square feet 2 tons 1,500 – 2,000 square feet 3 tons 2,000 – 2,500 square feet 4 tons.

How much does a 4 ton HVAC system cost?

Average AC Unit Prices by Size or Capacity Central AC Unit Size AC & Coil AC & Coil Installed Cost 2.5 Tons, 30,000 btu $1,525 $2,695 3 Tons, 36,000 btu $1,650 $2,990 3.5 Tons, 42,000 btu $1,780 $3,250 4 Tons, 48,000 btu $1,860 $3,350.

How many tons is 1200 square feet?

2 Tons Area (Square Feet): BTU Tonnage 600 sq ft 12,000 BTU 1 Ton 900 sq ft 18,000 BTU 1.5 Tons 1,200 sq ft 24,000 BTU 2 Tons 1,500 sq ft 30,000 BTU 2.5 Tons.

What size AC do I need for 3000 square feet?

For a home 1,501 to 1,800, the recommended capacity is 3 tons. For a 2,000 square-foot home, the best AC capacity is 3.5 tons. Since larger homes are costlier to cool, you’ll need a 5-ton unit to cool a 3,000 square-foot home.

Is the a big difference between a 2.5 ton and 3 ton AC?

The general guideline is a 2.5 ton unit for a home that’s 1,500 to 2,000 square feet. A 3 ton unit is ideal for a home that’s 2,000 to 2,500 square feet.

What size HVAC do I need for 1800 sq ft house?

Here’s some math: You need around 20 BTUs per square foot, which is equivalent to 0.0016 tons. For example, a 600-square-foot space requires a 12,000 BTU or 1-ton unit. By those calculations, an average 1,800-square-foot house would need a 3-ton central air conditioning unit.

What ton HVAC do I need?

To estimate your AC tonnage needs, multiply the number of square feet you’re cooling times 25. This equals the total number of BTUs you need to adequately cool your space. Next, divide that number by 12,000 to determine the tonnage capability you need in your new air conditioning unit.

What size air conditioner do I need for a 2400 square foot home?

The answer to the question, “what size AC unit for 2400 square feet?”, would be, is 60,000 BTUs or 5 Tons. It’s possible to fall between unit sizes, so if that’s the case with you, then you should choose the next higher size. That way, you can be sure that the AC unit can still cool a given area sufficiently.

What size air conditioner do I need for a 2200 square foot house?

For example, a 2,200 sq. ft. house divided by 600 = 3.6666. So you would want to install a 3.5 ton unit.

How big of an air conditioner do I need for 1600 square feet?

Assuming the minimum cooling capacity of 400 square feet per ton for your HVAC unit, a 1600 square foot home will require 4.0 tons of air conditioning to cool. Your HVAC unit will need to remove about 4.0 x 12,000 BTUs, or 48,000 BTUs, per hour to keep your home cool.

How much should a 3 ton air conditioner cost installed?

AC Installation Costs by Tons Central Air Conditioner Size AC Unit BTU AC Unit Only 2.5 Tons 30000 BTU $2,895 3 Tons 36000 BTU $2,920 3.5 Tons 42000 BTU $3,550 4 Tons 48000 BTU $3,650.

Why is HVAC rated in tons?

The use of tons to measure cooling capacity comes from this time. A ton refers to the amount of heat it takes to completely melt a ton of ice. Melting this amount of ice requires 286,000 Btu (British thermal units). Rounding up 11,917 Btu/hr gives you 12,000 Btu/hr, which is one ton of air conditioner capacity.

Can I replace a 3 ton AC with a 5 ton AC unit?

The short answer is, you can’t. A good tech might be able to get it to work with like a TXV, but you are going to be bottle-necked at the 3-ton. There is no way you will get 5-ton capacity after that. It will mess up your warranty and your efficiency will be off.