Table of Contents
As a rule of thumb, an air conditioner needs 20 Btu for each square foot of living space.
How many square feet can a 12000 BTU air conditioner cool?
The size of your space determines how much cooling capacity you need. Budget air conditioners range from 5,000 BTU, which can handle about 150 square feet, to 12,000 BTU, enough to cover about 550 square feet.
How many BTUs do I need for a 1500 square foot house?
A 1,500-square-foot home will require between 45,000 to 90,000 BTUs.
How many BTU do I need per square foot?
To determine the number of BTUs per square foot that you need to heat a room, simply multiply the square footage by 20 BTUs per square foot. For example, if a room has 1,000 square feet, you would require 20,000 BTUs to heat it.
How many BTU do I need for a 12×12 room?
6,000 BTU Room Type Room Size Recommended BTU 12 x 12 room 144 sq ft 6,000 BTU 12 x 24 room 576 sq ft 14,000 BTU 13 x 13 room 169 sq ft 6,000 BTU 14 x 16 room 224 sq ft 7,000 BTU.
How many rooms will a 8000 BTU air conditioner cool?
Air Conditioner BTU Chart; With 12,000 BTU (1 Ton) Room Size Example Cooling Capacity (BTU): Room/Area Size: 8,000 BTU air conditioner room size: 300-400 sq ft 10,000 BTU air conditioner room size: 400-500 sq ft 12,000 BTU air conditioner room size: 500-600 sq ft 14,000 BTU air conditioner room size: 600-700 sq ft.
How many sq ft does a 15000 BTU AC cool?
Those in the 12,000- to 15,000-Btu range cost from $450 to $600, while large units go up to $1,200. Air conditioners rated at 15,000 Btu should be enough to cool most rooms up to about 875 sq. ft.
Can a furnace be too big for a house?
Oversized furnaces can wreak havoc on your entire HVAC system, indoor air quality, and budget. Furthermore, it is expensive to operate a furnace that is too large. Your monthly energy costs will increase. Also, a system that is too large will require more repairs than one that is properly sized.
What size AC do I need for 1500 square feet?
Therefore, if your home is 1,500 square feet, your air conditioning unit should be 3.5 to four tons.
What size air conditioner do I need?
As a rule of thumb, an air conditioner needs 20 Btu for each square foot of living space. But other considerations, such as the ceiling height and the size of your windows and doorways, might call for more cooling power. To measure your room, multiply the length by the width.
How do I calculate BTU for my house?
For example, a 300 square foot room typically requires 7,000 BTUs to maintain a comfortable temperature, while a 1,000 square foot room requires 18,000 BTUs. A simple formula to determine your heating needs is: (desired temperature change) x (cubic feet of space) x . 133 = BTUs needed per hour.
What size air conditioner do I need for a 2400 square foot home?
The answer to the question, “what size AC unit for 2400 square feet?”, would be, is 60,000 BTUs or 5 Tons. It’s possible to fall between unit sizes, so if that’s the case with you, then you should choose the next higher size. That way, you can be sure that the AC unit can still cool a given area sufficiently.
How many BTU do I need for 3500 square feet?
157,500 BTU Home Size (Heating): Standard Climate Very Hot Climate 3,000 square feet 135,000 BTU 90,000 BTU 3,500 square feet 157,500 BTU 105,000 BTU 4,000 square feet 180,000 BTU 120,000 BTU 4,500 square feet 202,500 BTU 135,000 BTU.
How many BTU do I need for a 20×20 room?
Rule of thumb. A 1 ton (12,000 BTUH) unit is doable in the space you want to cool. To handle the hot, humid summer heat of your area, I would increase it to 15,000 – 16,000 BTUH.
What size room will a 10000 BTU air conditioner cool?
10,000 BTUs will cover 300 sq. ft. (2,400 cubic feet) 12,000 BTUs will cover 400 sq.
What size air conditioner do I need for a 3000 square foot house?
The recommended capacity for a home that is 1,201 to 1,500 square feet is 2.5 tons. For a home 1,501 to 1,800, the recommended capacity is 3 tons. For a 2,000 square-foot home, the best AC capacity is 3.5 tons. Since larger homes are costlier to cool, you’ll need a 5-ton unit to cool a 3,000 square-foot home.
Does higher BTU use more electricity?
The more BTU your unit produces, the more energy it consumes. So, if you are worried about high energy costs, you should get a unit that is appropriate for your space.
Is 9000 BTU enough for a bedroom?
Match the BTU rating to the room size Small rooms (150 square feet or below) will require a unit with around 6,000 BTUs. This is generally appropriate for a single bedroom. For larger rooms (up to 350 square feet), you will need a unit with around 9,000 BTUs. This is typical for most living rooms.
Is 8000 BTU enough for living room?
Consumer Reports recommends 20 BTUs per square foot of the living space (or spaces) you want to cool down. 300 – 350 sq. feet: 8,000 BTUs. 350 – 400 sq.
Can Window AC cool entire house?
Window air conditioners are designed to cool only a single room. It is very difficult for such AC to cool an entire house. At most you can cool two adjacently connected tiny rooms with a single window AC, but there will be uneven cooling.
How many square feet will a 25000 BTU air conditioner cool?
1,050 to 1,600 square feet: 18,500 to 25,000 BTU.
How many sq ft will 18000 BTU cool?
BTU Sizing Chart for Mini Split Systems Area To Be Cooled Capacity Needed (BTUs Per Hour) 450 to 550 square feet 12,000 BTUs 550 to 700 square feet 14,000 BTUs 700 to 1,000 square feet 18,000 BTUs 1,000 to 1,200 square feet 21,000 BTUs.