Table of Contents
A small window unit rated at 5,000 BTUs has a current draw of about 4 to 6 amps. A larger 12,000 BTU unit draws between 9 and 13 amps. Central air conditioning requires between 208 and 240 volts to operate and draws between 15 and 60 amps depending on the size.
How many amps does a 5000 BTU air conditioner use?
When plugged into a 110-volt outlet, most 5,000-BTU air conditioners use only 5 Amps. The range for window-unit air conditioners is between 5,000 and 18,000 BTUs.
What size breaker do I need for a window air conditioner?
So a wall/window air conditioner with a rating of over 7.5 amps would require its own circuit on a 15-amp breaker, or over 10-amps on a 20-amp breaker. If the applliance is not “fastened in place,” such as a portable dehumidifier, then it is allowed to be up to 80% of circuit rating, per NEC 210.23(A)(1).
How many amps does a 6000 BTU air conditioner use?
The small ambient air conditioners, usually in the range of 5,000 to 6,000 BTU, will pull between 5 and 7 amps of power. In most cases, they are connected in a wall socket that is served by a circuit breaker of 15 amps.
How many amps does a 9000 BTU air conditioner use?
The 9,000 BTU TTW air conditioner fits in a standard TTW sleeve. The unit requires 208/230 volts and 20 amps, and uses R-410A refrigerant. You’ll need a NEMA 6-20 receptacle to plug the unit in. The Heat Pump and Electronic control make it easy for users to change the room temperature to the desired setting.
How many amps does an 8000 BTU air conditioner use?
Table: How Many Amps Do Window, Portable, Mini-Split Air Conditioners Draw Air Conditioner Capacity Amperage (Estimate) AC Type: How many amps does an 8,000 BTU air conditioner use? 5.80 – 8.70 Amps Window AC, Portable AC How many amps does a 10,000 BTU air conditioner use? 7.25 – 10.87 Amps Window AC, Portable AC.
How many amps does a 12000 BTU portable AC?
At 120 volts the 12,000 btu a/c unit will draw approximately 29.3 amps. At 240 volts (220v) the A/C will draw approximately 14.75 amps.
Does a window unit need its own breaker?
Most window air conditioner units are 110/120 volts. These air conditioner units that require 7 or more amps to operate will need their own dedicated circuits. If you do not have a dedicated air conditioner circuit, a professional electrician will need to install one for you.
How many amps does a 220 window unit pull?
Most common voltage ratings for AC units are 115, 125 and 220 volts, and amperage rating can run from 15 to 20 amps. The lower two voltage ratings are common in smaller units, while units with a rating higher than 15,000 BTUs will require a 220-volt circuit.
Does a window air conditioner need its own circuit?
Window AC units are typically easy to install, and most provide an energy saver switch option that makes them affordable to operate when you only need to cool one room. With a few exceptions, most window air conditioners will require their own dedicated circuit so they don’t overload an existing room circuit.
How many amps does a 15000 BTU air conditioner use?
On average, a 15,000 BTU air conditioning unit draws around 12.5 amps.
How many amps does a 1.5 hp air conditioner use?
Answer: 20 Amp circuit breaker is enough for a 1 HP motor air conditioner.Circuit breaker for air conditioner table. Circuit breaker for 0.5 HP Air Conditioner 15 Amp or higher Circuit breaker for 1.5 HP air conditioner 30 Amp or higher.
How many amps is 1000 watts?
8.33 Amps Watts: Amps (at 120V): 1000 Watts to amps at 120V: 8.33 Amps 1100 Watts to amps at 120V: 9.17 Amps 1200 Watts to amps at 120V: 10.00 Amps 1300 Watts to amps at 120V: 10.83 Amps.
What is the highest BTU air conditioner for 110 volts?
The highest BTU a 110V window air conditioner can generate is 15,000 BTU (you will find one example of 15,000 BTU 110V window AC below). Window air purifiers can achieve almost 30,000 BTU cooling output if hooked up to 230V.
How do you convert BTU to amps?
1 btu per hour ≈ 0.2931 volt-ampere.
How many watts does a 8000 BTU air conditioner use?
A mid-size 8,000 BTU AC should use fewer than 715 watts. A big 14,000 BTU air conditioner should only use 1,250 watts.
What size breaker do I need for a 10000 BTU air conditioner?
1 watt = 3.41 BTU’s so a 10,000 btu air conditioner would equal 2932 watts and use 24 amps at 120 volts and 12 amps at 240 volts.
How many amps does a 16000 BTU air conditioner draw?
Then there are the 16,000 Btu air conditioners we tested that typically run at around 9-10 amps and have a peak measured inrush current of 72 amps. That size air conditioner will normally bog down a Honda 2000i portable generator on start-up unless an EasyStart soft start device is installed.
How many amps does it take to run a 14000 BTU air conditioner?
14,000 BTU – Remote Control – 3-Speed Control Panel – 1340 Watts – 120 Volts – 11.7 Amps – 6 ft. Power Cord – Active Air ACAN14.
How much electricity does a 13000 BTU air conditioner use?
How Many Watts Does A Window AC Use? (500 – 2,500W) Window AC Unit Capacity (in BTU): Power Draw (in Watts): 11,000 BTU 1,100 watts 12,000 BTU 1,200 watts 13,000 BTU 1,300 watts 14,000 BTU 1,400 watts.
Why does my portable AC unit keep tripping the breaker?
Well, an air conditioner usually trips the breaker because it’s pulling in more amps than the breaker is rated for. That is, if you have a 20-amp breaker and the AC pulls 30 amps, the breaker trips. That’s why breakers trip: to protect you from overcurrents that can damage equipment and cause fires (yikes).
Can I plug a portable air conditioner into a regular outlet?
Yes, you can. This is also true for power strips and surge protectors. An AC can easily overload these devices. It can start fires by causing the plugs and cables of power strips, extension cords, and surge protectors to overheat.
Can you use an extension cord for a window air conditioner?
First and foremost: do not connect your air-conditioner window unit to an extension cord. There are heavy-duty extension cords that are specifically designed for major appliances like air-conditioners. These should be shorter cords with lower gauges (12 or 14 gauge) and higher amp ratings.
How many watts does a window AC use?
A large window AC uses up to 1,440 watts, a medium one uses 900 watts, and a small model uses about 500 watts. You can calculate the energy consumption level of an AC by using the information on the label. Check the energy-saving label for the annual power consumption rate of the system.
Does a window AC need a GFCI outlet?
GFCI protection is never required for an outlet supplying an HVAC unit.