Table of Contents
According to a basic industry standard, a 5,000 BTU air conditioner can cool a room that is 100 to 150 square feet.
How many BTU do I need for a 12×12 room?
6,000 BTU Room Type Room Size Recommended BTU 12 x 12 room 144 sq ft 6,000 BTU 12 x 24 room 576 sq ft 14,000 BTU 13 x 13 room 169 sq ft 6,000 BTU 14 x 16 room 224 sq ft 7,000 BTU.
Is 5000 BTU enough for a room?
According to the EPA’s rule of thumb role, 5000 BTU room size should be 250 sq ft. If you have a 150 sq ft room to cool, 5000 BTU will be more than enough. However, EPA in their rule of thumb specifically recommends that we should calculate: “20 BTU of cooling output per 1 sq ft.”.
How many BTU do I need for a 20×20 room?
Rule of thumb. A 1 ton (12,000 BTUH) unit is doable in the space you want to cool. To handle the hot, humid summer heat of your area, I would increase it to 15,000 – 16,000 BTUH.
Will 5000 BTU cool an apartment?
A 5,000 Btu air conditioner can effectively cool a room that measures 100 to 150 square feet, according to a basic industry standard. Therefore, the best way to choose an air conditioner capacity is to start with the room’s square footage, and then make adjustments as needed for the specific space.
Does a 6000 BTU air conditioner cool?
In general, a 5,000 to 6,000 BTU air conditioner can cool between 100 and 300 square feet. Seven thousand to 8,200 BTU units are adequate for cooling 250 to 550 square feet, while 9,800 to 12,500 BTU models cool up to 950 square feet.
What is 5000 BTU air conditioner?
The 5,000 BTU AC units are as low as you can possibly go with stationary air conditioners. If we use the EPA’s cooling coverage minimal rule of ’20 BTU per sq ft’, the 5,000 BTU air conditioners are capable of cooling down rooms up to 250 sq ft.
How many BTU is good for an AC?
According to the US Department of Energy directive, an air conditioner’s most appropriate size would be 2,880 BTU unit. The best you can do here is to buy a small 5,000 BTU window or a small 8,000 BTU portable AC unit (more about the smallest AC units here).
How many watts does it take to run a 5000 BTU air conditioner?
For a small bedroom, a 5,000 BTU window unit should only use 450 watts. A mid-size 8,000 BTU AC should use fewer than 715 watts.
How many square feet will 5200 BTU heat?
170 sq. ft Heater Capacity (BTU): Room Size: 5,000 BTU 160 sq. ft. 5,100 BTU 170 sq. ft. 5,200 BTU 170 sq. ft. 6,000 BTU 200 sq. ft.
Will higher BTU cool faster?
If you’re wondering if an air conditioner with higher BTU’s will cool your room faster, it is possible, but it depends. It also depends on the total cubic feet of the room to be cooled, so if the ceiling height is higher than 10 feet, that is added cubic feet which requires additional cooling power or more BTU’s.
How much space can a 14 000 BTU air conditioner cool?
Medium rooms: For rooms between 350 and 700 square feet, you’ll want a 11,000-to-14,000 BTU unit. This 12,000-BTU SereneLife air conditioner says it cools rooms up to 450 square feet. Large rooms: Residential units generally top out around 14,000 BTU, enough for 700 square feet at most.
How many BTUs do I need to cool my house?
Size and Ceiling Height Area To Be Cooled (square feet) Capacity Needed (BTUs per hour) 450 to 550 12,000 550 to 700 14,000 700 to 1,000 18,000 1,000 to 1,200 21,000.
Is there a big difference between 5000 BTU and 6000 BTU?
Keep in mind that a 5000 BTU AC is rated for “up to” 150 square feet and a 6000 BTU unit is rated for “up to” 250 square feet. In simple terms, that a room 10×15 (150 square feet) or about 15×17 (about 250 square feet). Those are the biggest areas these units can effectively cool and dehumidify.
Does higher BTU use more electricity?
The more BTU your unit produces, the more energy it consumes. So, if you are worried about high energy costs, you should get a unit that is appropriate for your space.
Is 6000 BTU enough for a living room?
Consumer Reports recommends 20 BTUs per square foot of the living space (or spaces) you want to cool down. 150 – 250 sq. feet: 6,000 BTUs.
Is there a big difference between 5000 and 6000 BTU air conditioner?
The difference between a 5000 BTU vs 6000 BTU air conditioner is that the 5000 BTU unit covers 100 to 150 square feet while a 6000 BTU unit will cover 150 to 250 square feet. Therefore, 6000 BTU air conditioners are suitable for larger rooms than the 5000 BTUs.
How many BTU should a bedroom have?
Generally, your temperature control system should have 20 BTU for every square foot of living space in the area you wish to heat or cool. For example, if your room or area is 400 square feet in size, then you should opt for a temperature control system with a capability of around 8,000 BTU.
Is 8000 BTU enough for a bedroom?
Recommended BTU By Room Size If you are looking for an air conditioner for a room measuring say 10′ x 15′ (150 square feet), the recommended BTU range is up to 5400. Once you get into 340 and 400 square feet per room, you’d need an 8,000 or 9,000 BTU air conditioner, respectively.