QA

Quick Answer: How Big Ac For 1500 Square Feet

What size AC do I need for 1500 square feet?

Therefore, if your home is 1,500 square feet, your air conditioning unit should be 3.5 to four tons.

How many square feet will a 3 ton AC cool?

3-ton is equal to 36,000 BTU. If you apply the 20 BTU per sq ft rule of thumb, you can see that a 3-ton air conditioner cools about 1,800 square feet spaces.

What size air conditioner do I need for 1600 square feet?

Assuming the minimum cooling capacity of 400 square feet per ton for your HVAC unit, a 1600 square foot home will require 4.0 tons of air conditioning to cool. Your HVAC unit will need to remove about 4.0 x 12,000 BTUs, or 48,000 BTUs, per hour to keep your home cool.

How many square feet does a 2 ton AC cool?

ZONE 1 ZONE 2 1.5 Tons 600 – 900 sf 600 – 950 sf 2 Tons 901 – 1200 sf 951 – 1250 sf 2.5 Tons 1201 – 1500 sf 1251 – 1550 sf 3 Tons 1501 – 1800 sf 1501 – 1850 sf.

How many sq ft will a 2.5 ton AC cool?

For example, a 30,000 BTU, 2.5-ton air conditioner is made to effectively cool a home between 1,200 and 1,500 square feet. A slightly larger 3,600, 3-ton unit, is designed for homes that are 1,500 to 1,800 square feet.

Which AC is suitable for 12×12 room?

According to Energy Star, a 12×12′ or 144 sqft room requires 5,000 BTU of cooling capacity when occupied by two persons. If the room is heavily shaded, it only requires 4,500 BTU. If the room is very sunny, it requires 5,500 BTU. For each additional person, you need to add 600 BTU.

Is 3 ton AC big enough?

Pro Tip: as a rule of thumb, the maximum AC unit size you need to install should not be more than 15% more than the BTU’s you need to cool your house. This means that if your house requires a 24,000 BTU unit (2 tons), you should not install one that is larger than 30,000 BTU’s (3 tons) to maintain energy efficiency.

Is 2.5 ton AC big enough?

According to this common but somewhat inaccurate method, you need 1 ton of air cooling capacity for every so many square feet of living space. While there’s some dispute over the exact amount, an often-used amount is 600 square feet. A 2.5-ton unit, then, theoretically would fit a 1,500-square-foot home.

Can you replace a 2 ton AC unit with a 3 ton?

Simple answer: yes. But that really depends on the size of you house and its condition. If the 2 ton unit is working as designed but seems to run continuously without satisfying the thermostat setting, then it might be undersized and replacing it with a 3 ton unit might be the answer.

What size AC unit do I need for a 1300 sq ft house?

When looking for the quick answer to how much air-conditioning power you’ll need to adequately cool a 1,300-square-foot space, the answer is 23,000 BTUs per hour of air conditioning power. This is the base capacity needed for a 1,200- to 1,400-square-foot house.

What size AC do I need for 1800 sq ft house?

Here’s some math: You need around 20 BTUs per square foot, which is equivalent to 0.0016 tons. For example, a 600-square-foot space requires a 12,000 BTU or 1-ton unit. By those calculations, an average 1,800-square-foot house would need a 3-ton central air conditioning unit.

What size AC do I need for 1200 sq ft?

STEP 1: Determine how many BTUs of heating and tons of AC you need House Square Footage BTUs Needed 500 – 700 14,000 700 – 1,000 18,000 1,000 – 1,200 21,000 1,200 – 1,400 23,000.

What is the difference between 1.5 ton and 2 ton AC?

The capacity of 1.5 ton AC is 18000 BTU per hour in this way the capacity of 2 ton AC is 24000 BTU per hour. But now a days all AC available in the market for having capacity 22,000 BTU per hour are said to 2 ton .

Is the a big difference between a 2.5 ton and 3 ton AC?

The general guideline is a 2.5 ton unit for a home that’s 1,500 to 2,000 square feet. A 3 ton unit is ideal for a home that’s 2,000 to 2,500 square feet.

Is a 2 ton AC big enough?

For those of you that don’t understand the way AC systems work, a 2-ton unit typically provides cooling for about 900-1,400 square feet of space – give or take.

How much should a 3 ton AC unit cost installed?

AC Installation Costs by Tons Central Air Conditioner Size AC Unit BTU AC Unit Only 2.5 Tons 30000 BTU $2,895 3 Tons 36000 BTU $2,920 3.5 Tons 42000 BTU $3,550 4 Tons 48000 BTU $3,650.

What is the room size for 1.5 ton AC?

Room size and power consumption For instance, a 1-ton window AC or a 1.5 ton split AC is an ideal choice for rooms measuring up to 150-160 sq ft.

Do I need a 4 ton or 5 ton AC unit?

The answer to the question, “what size AC unit for 2400 square feet?”, would be, is 60,000 BTUs or 5 Tons. It’s possible to fall between unit sizes, so if that’s the case with you, then you should choose the next higher size.