Table of Contents
For general use receptacles, In commercial buildings it is limited to 180VA per duplex or single receptacle, therefore on a 12/2 Romex cable not otherwise subject to ampacity derating and protected by a 20 amp circuit breaker, that would allow a maximum of 13 receptacles.
How many outlets can you put on a 20 amp circuit with a 12-2 wire?
Generally speaking, 10 on a 20 amp branch circuit and 8 on a 15 amp branch circuit. The 12–2 wire would be required for a 20 amp circuit. However, this is based on a load calculation method that uses 1.5amps per receptacle and the 80% rule (your 20 amp circuit should not be loaded above 16 amps).
Can you use 12-2 wire for lights and outlets?
Yes, it is okay to use 12-2 cable to supply lighting fixtures. The other answer indicates that it even with 12-2 you have to use a 15A breaker for lighting circuits which is not strictly correct. If the entire circuit is 12AWG (other than fixture wires), then a 20A breaker may be used.
How many amps can a 12-2 wire handle?
Maximum Breaker Size is 30 amps. You can use a 20 amp circuit breaker with 12/2 Romex as 12/2 wire is rated for 20 amps.
How many outlets can I put on a 12 2 wire?
For general use receptacles, In commercial buildings it is limited to 180VA per duplex or single receptacle, therefore on a 12/2 Romex cable not otherwise subject to ampacity derating and protected by a 20 amp circuit breaker, that would allow a maximum of 13 receptacles.
How far can you run 12 gauge wire on a 20 amp circuit?
You can run a 12 gauge wire up to 70 feet on a 15 amp circuit. That number drops to 50 feet if you run 12 gauge wire on a 20 amp circuit.
How long can I run 12 2 wire?
You can run 50′ on a 12 gauge wire. I can’t imagine why you would want to run a number 12 any further than 50′. If you have to go that far you are better to have 30–50+ amp with 2 phases’ and a sub panel with breakers. This way you can run multiple things.
How many lights can you put on one switch?
There is no limit to the number of lights on a circuit. The load of the fixtures is what determines how many lights a circuit can accommodate. A conventional 15A circuit can have up to 1400W of lighting loads connected to it. A 1400 Watts lighting load can accommodate one 1400W fixture or fourteen 100W fixtures.
Is it OK to mix 12 and 14 gauge wire?
Originally Answered: Can I mix 12 and 14 gauge wire? The 12 gauge can carry more current, therefore; you must not use 14 gauge in place of 12 gauge, but you can use 12 gauge in place of 14 gauge, but 12 gauge is larger.
What can 12-2 wire be used for?
A 12-3 Romex will have a black(hot), red(hot), white(neutral), and bare copper. The red on a 12-3 is used for three-way light switches which are covered later.The following NEC regulations apply to Romex conductors: Wire Gauge or Type Rated Amperage Common Uses 12-2 Romex 20 A Lighting and Outlet Circuits, refrigerator.
Can you run 12 gauge wire on a 30 amp breaker?
You should not use a 30-amp circuit breaker on a 12-gauge wire. The circuit breaker installed on a circuit is of a specific size to protect a certain wire gauge. This higher current can damage the thinner wire, melt the insulation, cause short circuits, fire, and even lethal shock.
Can I use 12 gauge wire on a 15 amp breaker?
Because it has even less chance of overheating, 12-gauge wire is also acceptable on a 15-amp circuit.
Can I wire lights and outlets on the same circuit?
Yes, you can. The average home uses an indoor distribution board that houses the breakers of the majority of circuits in the home. A circuit controlled by a 15A circuit breaker (which a lot of contractors use for general lighting) can also accommodate outlets.
Should you wire outlets in series or parallel?
But, in fact, all household receptacles are always wired in parallel, and never in series. In a series circuit, current must pass through a load at each device.
When installing a receptacle in which direction should the ground face?
The electrical code allows outlets to be installed with the ground plug hole facing up, down or sideways. It’s up to you, there is no standard electric outlet orientation. So that means there really is no such thing as upside down outlets.
How many outlets can I put on a 15 amp breaker?
Technically, you can have as many outlets on a 15 amp circuit breaker as you want. However, a good rule of thumb is 1 outlet per 1.5 amps, up to 80% of the capacity of the circuit breaker. Therefore, we would suggest a maximum of 8 outlets for a 15 amp circuit.
How many outlets can I run on a 20 amp breaker?
The answer to the question how many outlets on a 20 amp circuit is ten outlets. Always comply with the 80% circuit and breaker load rule, allowing a maximum load of 1.5 amps per receptacle. Remember that your circuit, wire sizes, and outlets must be compatible to avoid overheating and electrical hazards.
What size wire do I need for a 110 outlet?
To wire a 110 volt/120 volt outlet, you need 3 wires, green or bare copper is the ground, white is neutral, and usually black or red is the hot (live) wire (in this case my Hot is the purple wire). In the home, you will usually use Romex wire that you can get at the hardware store.