Table of Contents
GFCI outlets should be installed in any potentially wet or damp areas such as kitchens, bathrooms, laundry rooms, outdoors, basements, garages and workshops. Damp areas can make you prone to dangerous electric shock but using a GFCI outlet can greatly reduce your risk of injury.
Can I put a GFCI outlet anywhere?
You can replace almost any electrical outlet with a GFCI outlet. Correctly wired GFCIs will also protect other outlets on the same circuit. The electrical code also requires GFCIs in unfinished basements, garages, most outdoor receptacles and places where construction activity occurs.
Do all outlets in kitchen need to be GFCI?
In kitchens, all outlets that serve countertop surfaces should be equipped with GFCI outlet protection. That would include any outlets on walls, behind wet areas (sinks, etc.) that have features such as countertop breakfast bars (open counter surfaces above sinks used to sit at on the opposite side).
How many GFCI outlets can be on a circuit?
The Standard Number Of GFCI’s On One Circuit Keep in mind, you only need one GFCI at the beginning of the circuit for GFCI protection for the whole circuit. You might even opt for a GFCI rated breaker instead.
Can you put 2 GFCI outlets on the same circuit?
Yes, you can have many GFCI outlets on the same circuit The way they vary from a regular outlet is they check for ground faults.
Does a refrigerator need a GFCI?
A refrigerator shouldn’t be plugged into a GFCI outlet. GFCI outlets are used in areas of the home with water or moisture. These include bathrooms, basements, and kitchens. This type of outlet is important because it reduces the risk of electrocution and electrical fires.
How close to a sink DO YOU NEED A GFCI?
As a rule of thumb, any outlet within six feet of the sink should be a GFCI outlet.
Where should a GFCI be placed in a kitchen?
Kitchens: All receptacles serving countertop areas and any receptacle within 6 feet of a sink must have GFCI protection. Also, the receptacle supplying a dishwasher should be GFCI-protected.
Does power go to line or load on GFCI?
The “line” wires are the incoming power from the breaker box and the “load” wires are the outgoing power that travels down the circuit to the next outlet.
Does every outlet in a garage need to be GFCI?
All garage outlets must be GFCI. It is an electrical violation to have non-GFCI outlets in your garage. The NEC (National Electrical Code) made this a requirement in 2008. GFCI outlets in your garage can save you from electrical failures and shock.
Can you put GFCI at end of run?
If your objective is to protect just one outlet, for instance, an outlet in the kitchen, and that outlet happens to be at the end of the circuit, you can install a GFCI on an outlet at the end of the circuit. Yes, it makes more sense to place it at the start because that allows you to defend all the outlets downstream.
What is the load side?
The load side is where the power leaves the device (or electrical box) and travels down the circuit.
What happens if you hook up a GFCI backwards?
If you miswired the GFCI it may not prevent personal injury or death due to a ground fault (electrical shock). If you mistakenly connect the LINE wires to the LOAD terminals, the GFCI will not reset and will not provide power to either the GFCI receptacle face or any receptacles fed from the GFCI.
What happens if you switch line and load on GFCI?
Here’s what happens when somebody wires a GFCI receptacle with the load and line wires reversed: The GFCI will work, in the sense that you can plug in a hair dryer and the hair dryer will blow hot air. If the load and line wiring gets messed up, a ground fault (radio in the tub) won’t trip the GFCI.
How many GFCI outlets can be on a 15 amp circuit?
Technically, you can have as many outlets on a 15 amp circuit breaker as you want. However, a good rule of thumb is 1 outlet per 1.5 amps, up to 80% of the capacity of the circuit breaker. Therefore, we would suggest a maximum of 8 outlets for a 15 amp circuit.
Can you wire GFCI outlets in series?
But we can also wire them in series. However, when there is some type of load exists then there is a possibility that we may not be unable to get correct values of voltages at the other outlets of our application, having a series connection of GFCI. So always try to connect GFCI outlets in parallel.
Can you put GFCI in series?
You only need 1 GFCI outlet per circuit (assuming it’s at the beginning of the line and the rest of the outlets are loads). They are correctly wired in parallel – if they were in series, you wouldn’t get the correct voltage at the other outlets when there is any type of load present.
Should a freezer be plugged into a GFCI outlet?
However, GFCI’s are prone to a phenomenon called “phantom tripping,” meaning that they sometimes activate -shutting power off to the circuit – under normal, everyday voltage fluctuations. So freezers and refrigerators should never be plugged into GFCI’s.
Should microwave be on GFCI?
A GFI or GFCI outlet is needed if the microwave is located less than 6 feet from a water source such as the edge of the sink, toilet, shower, etc. It is also needed if located outdoors, garages, kitchen counter tops, near laundry, utility sinks, wet bar sinks and near swimming pools.
Should a dishwasher be on a GFCI?
Kitchen dishwashers installed in dwelling units require GFCI protection whether hard wired or cord and plug connected. Code Change Summary: A new subsection was added regarding dwelling unit kitchen dishwashers. Now, outlets that supply dwelling unit kitchen dishwashers must have GFCI protection.