Table of Contents
STEP 1: Determine how many BTUs of heating and tons of AC you need House Square Footage BTUs Needed 500 – 700 14,000 700 – 1,000 18,000 1,000 – 1,200 21,000 1,200 – 1,400 23,000.
How many BTUs do I need for a 1300 square foot house?
How many btu do I need to heat 3,000 square feet? Room/Area Size Heating Capacity(BTU) 1,000 sq ft 45,000-55,000 BTU 1,200 sq ft 55,000-65,000 BTU 1,300 sq ft 59,000-71,000 BTU 1,400 sq ft 63,000-77,000 BTU.
What size furnace do I need for a 1300 square foot home?
Chart For Furnace Tonnages And BTUs For 500 – 3,000 Sq Ft Houses House Size (Sq Ft): Furnace Size (in BTUs): 1000 sq ft home 45,000 BTU furnace 1100 sq ft home 49,500 BTU furnace 1200 sq ft home 54,000 BTU furnace 1300 sq ft home 58,500 BTU furnace.
What ton AC do I need for 1200 square feet?
DIY Calculations Square Footage BTUs per hour AC Unit Tonnage 1,000 to 1,200 21,000 2 Tons 1,200 to 1,400 23,000 2 Tons 1,400 to 1,500 24,000 2 Tons 1,500 to 2,000 30,000 2.5 Tons.
How many square feet will a 60 000 BTU furnace heat?
How Many Square Feet Will 30,000 – 120,000 BTU Furnace Heat? Furnace Capacity Square Footage(Hot Climate) Square Footage(Moderate Climate) 60,000 BTU 2,000 sq ft 1,320 sq ft 70,000 BTU 2,320 sq ft 1,550 sq ft 80,000 BTU 2,650 sq ft 1,760 sq ft 90,000 BTU 3,000 sq ft 2,000 sq ft.
How much is an air conditioner for a 1200 square foot house?
Cost of Central Air for a 1,200 Square Foot House The cost to install central air in a 1,200 square foot home sits between $3,000 and $4,000. Of course, this price varies based on the SEER rating of the unit, and whether or not the home requires ductwork installation or repair.
What size AC unit do I need for a 1400 sq ft house?
ZONE 1 ZONE 5 1.5 Tons 600 – 900 sf 700 – 1100 sf 2 Tons 901 – 1200 sf 1101 – 1400 sf 2.5 Tons 1201 – 1500 sf 1401 – 1650 sf 3 Tons 1501 – 1800 sf 1651 – 2100 sf.
What size furnace do I need for 1200 square feet?
A 1,200-square-foot home will require between 35,000 and 75,000 BTUs. A 1,500-square-foot home will require between 45,000 to 90,000 BTUs. A 1,800-square-foot home will require between 55,000 to 110,000 BTUs. A 2,100-square-foot home will require between 65,000 to 125,000 BTUs.
Is it better to undersize or oversize a furnace?
Heating systems should never be undersized to prevent discomfort when outdoor temperatures or weather conditions exceed the capacity of the heating source. Although over sizing a heating system can be equally uncomfortable if grossly oversized which can cause large temperature swings and frequent cycling.
Can a furnace be too big for a house?
Oversized furnaces can wreak havoc on your entire HVAC system, indoor air quality, and budget. Furthermore, it is expensive to operate a furnace that is too large. Your monthly energy costs will increase. Also, a system that is too large will require more repairs than one that is properly sized.
How big of a house will a 2 ton AC unit cool?
Step 5: Match your square footage to an HVAC size chart Home Sq Footage Air Conditioner Size (tons) 600 – 1,000 square feet 1.5 tons 1,000 – 1,500 square feet 2 tons 1,500 – 2,000 square feet 3 tons 2,000 – 2,500 square feet 4 tons.
Which AC is suitable for 12×12 room?
According to Energy Star, a 12×12′ or 144 sqft room requires 5,000 BTU of cooling capacity when occupied by two persons. If the room is heavily shaded, it only requires 4,500 BTU. If the room is very sunny, it requires 5,500 BTU. For each additional person, you need to add 600 BTU.
What SEER AC should I get?
For most homeowners, opting for a unit with a SEER between 15 and 18 is a good choice because it’s a balance between the money you’ll spend for the unit and the amount you’ll save on utility costs.
What size furnace do I need for a 1000 sq ft house?
A basic rule of thumb is that it takes 30 BTUs for every 1,000 square feet. At the most basic level, if you have a 1,000 square foot house, you’ll look for a furnace that has 30,000 BTU output.
How big of a furnace do I need for a 1500 sq ft house?
Generally in a Californian climate you will need 25-30 BTU per square foot. BTU is a measurement of a furnace’s heat output. 1500 sq feet by 25 BTU gives us a 37,500 BTU furnace.
How big of a house can a 60000 BTU furnace heat?
A standard that is used by heating and cooling equipment companies is to provide at least 25 to 30 Btu of heat per square feet in the home for a moderate to warm climate. A mid-sized home of 2,000 square feet would need approximately 50,000 to 60,000 Btu to heat it properly.
How much is a new AC unit for a 1300 square-foot house?
For a 1,300 to 1,600 square ft home you would want a 2.5 ton AC unit and the average installation cost would be around $3,570 with the unit alone costing around $1,285.
How much is a new AC unit for a 1400 sq ft house?
AC Unit Cost Based On Size Area (sq.ft) Unit Capacity (BTU) Installation Cost 700 – 1,000 18,000 $2,200 – 3,300 1,200 – 1,400 21,000 $3,000 – 3,800 1,500 – 2,000 30,000 $3,500 – 4,300 2,000 – 2,500 34,000 $4,500 – 5,000.
How much is a furnace for a 1200 square-foot house?
Cost of a Furnace for a 1,200 Sq. ft. home is between $700 and $2,200. This assumes you are using an electric unit in zone 2 or another type in zone 4. Having a home in a warmer or colder climate could impact the unit size.