QA

How Many Btus Per Room

Size and Ceiling Height Area To Be Cooled (square feet) Capacity Needed (BTUs per hour) 450 to 550 12,000 550 to 700 14,000 700 to 1,000 18,000 1,000 to 1,200 21,000.

How do you calculate BTU for a room?

For each room, multiply the BTU per square footage times the square footage of the room. For example, a home located in Zone 5 with poor insulation would require 60 BTUs per square foot. Therefore, a room that is 300 square feet will need 18,000 BTUs (60 x 300).

How many BTU do I need for a 12×12 room?

6,000 BTU Room Type Room Size Recommended BTU 12 x 12 room 144 sq ft 6,000 BTU 12 x 24 room 576 sq ft 14,000 BTU 13 x 13 room 169 sq ft 6,000 BTU 14 x 16 room 224 sq ft 7,000 BTU.

How many BTUs is 1hp aircon?

When choosing an air conditioner, usually a 1 HP (horse power) equipment is able to remove 9,000 BTU/hr of heat. With better technology, some machines are able to remove 10,000 BTU/hr of heat with the same capacity. The higher the listed BTU/hr, the greater the cooling capacity.

How many BTU do I need for a 20×20 room?

Rule of thumb. A 1 ton (12,000 BTUH) unit is doable in the space you want to cool. To handle the hot, humid summer heat of your area, I would increase it to 15,000 – 16,000 BTUH.

What size room will 5000 BTU cool?

The size of your space determines how much cooling capacity you need. Budget air conditioners range from 5,000 BTU, which can handle about 150 square feet, to 12,000 BTU, enough to cover about 550 square feet. Naturally, air conditioners with higher capacities have higher price tags.

How many sq ft does a 15000 BTU AC cool?

Those in the 12,000- to 15,000-Btu range cost from $450 to $600, while large units go up to $1,200. Air conditioners rated at 15,000 Btu should be enough to cool most rooms up to about 875 sq. ft.

Is 8000 BTU enough for a bedroom?

Recommended BTU By Room Size If you are looking for an air conditioner for a room measuring say 10′ x 15′ (150 square feet), the recommended BTU range is up to 5400. Once you get into 340 and 400 square feet per room, you’d need an 8,000 or 9,000 BTU air conditioner, respectively.

Is 1hp aircon enough?

1) Horsepower – How much is needed? The basic rule of thumb is the bigger the room is, the higher the cooling capacity is required. Another factor to consider is the amount of heat exposure the room has during the day. If the room has direct sunlight, it might need bigger HP to bring the temperature down.

How much HP is needed for a room?

TIP 1: Match your aircon horsepower (HP) to the size of your room Room Size Aircon Horsepower (HP) 12 to 17 sq. m 0.75 HP 18 to 22 sq. m 1.0 HP 23 to 27 sq. m 1.5 HP 28 to 40 sq. m 2.0 HP.

How do I find the aircon capacity of a room?

Aircon capacity to room size guide To get a rough calculation, multiply your room size by 500. So if your room is 10 sqm. in size, you need an aircon with 5,000 kJ/hr of cooling capacity – which most 0.5 HP window type aircons have.

What size room will a 18000 BTU air conditioner cool?

800-900 sq ft Cooling Capacity (BTU): Room/Area Size: 14,000 BTU air conditioner room size: 600-700 sq ft 16,000 BTU air conditioner room size: 700-800 sq ft 18,000 BTU air conditioner room size: 800-900 sq ft 20,000 BTU air conditioner room size: 900-1,000 sq ft.

What size air conditioner do I need for a 2400 square foot home?

The answer to the question, “what size AC unit for 2400 square feet?”, would be, is 60,000 BTUs or 5 Tons. It’s possible to fall between unit sizes, so if that’s the case with you, then you should choose the next higher size. That way, you can be sure that the AC unit can still cool a given area sufficiently.

What size aircon do I need?

As a general rule we advise you to buy an Air Conditioner with a minimum 7000BTUs as this is the minimum required to call a small room (18sq/m) on a hot day. Medium rooms (24sq/m) need around 10,000BTUs and larger rooms and office spaces (36sq/m) require around 15000BTUs.

Is it cheaper to leave the AC on all day?

In general, it is cheaper to leave the AC on all day during very hot temperatures. However, turning off the AC during a heat wave can quickly introduce a lot of heat and humidity into your home. After even just a couple of hours, your AC will have to work hard to lower the temperature back to a comfortable level.

Is it cheaper to run a window air conditioner or central air?

A window unit comes in at a way cheaper price of around $300-$1,500 with monthly running costs of about $30-$80 depending on its usage. However, if you’re planning to cool more than 5 rooms, then one central air conditioner will be cheaper in the long run.

Does higher BTU use more electricity?

The more BTU your unit produces, the more energy it consumes. So, if you are worried about high energy costs, you should get a unit that is appropriate for your space.

What size room will a 12000 BTU cool?

A 12000 Btu unit will effectively cool a room with a floor space of 500 to 600 square feet.

What size room will a 12 000 BTU air conditioner cool?

12,000 BTUs will cover 400 sq. ft. (3,200 cubic feet) 13,000 BTUs will cover 450 sq.

Are two air conditioners better than one?

Two units allow for an easier time balancing the desired temperature in your home. Generally, one area of your home will be warmer or more difficult to cool than another. In a two-story home, the upstairs area is often warmer, as warm air rises. Having two AC units in your home can help balance out the temperature.