QA

Quick Answer: How Many Btu Cooling Per Square Foot

The Rules for Keeping Cool As a rule of thumb, an air conditioner needs 20 Btu for each square foot of living space.

How many BTU do I need per square foot?

To determine the number of BTUs per square foot that you need to heat a room, simply multiply the square footage by 20 BTUs per square foot. For example, if a room has 1,000 square feet, you would require 20,000 BTUs to heat it.

How do I calculate BTU for cooling?

All you have to do is to multiply the length of your room in feet by the width of your room in feet, and then multiply that by 25. That will give you the BTU needed to properly cool your room. All it takes is a simple multiplication!Oct 16, 2019.

How many BTU do I need for a 12×12 room?

6,000 BTU Room Type Room Size Recommended BTU 12 x 12 room 144 sq ft 6,000 BTU 12 x 24 room 576 sq ft 14,000 BTU 13 x 13 room 169 sq ft 6,000 BTU 14 x 16 room 224 sq ft 7,000 BTU.

How many BTUs do I need for a 2000 square foot house?

Heating BTUs Table (Rough Estimates) Home Size (Heating): Standard Climate Very Cold Climate 1,500 square feet 67,500 BTU 90,000 BTU 2,000 square feet 90,000 BTU 120,000 BTU 2,500 square feet 112,500 BTU 150,000 BTU 3,000 square feet 135,000 BTU 180,000 BTU.

What size AC do I need for 1200 sq ft?

STEP 1: Determine how many BTUs of heating and tons of AC you need House Square Footage BTUs Needed 500 – 700 14,000 700 – 1,000 18,000 1,000 – 1,200 21,000 1,200 – 1,400 23,000.

How many BTUs do I need to cool 1000 square feet?

How to Calculate Size Air Conditioning Sizing Chart: 450 to 550 sq ft 12,000 BTUs 550 to 700 sq ft 14,000 BTUs 700 to 1,000 sq ft 18,000 BTUs 1,000 to 1,200 sq ft 21,000 BTUs.

What size room will 5000 BTU cool?

The size of your space determines how much cooling capacity you need. Budget air conditioners range from 5,000 BTU, which can handle about 150 square feet, to 12,000 BTU, enough to cover about 550 square feet. Naturally, air conditioners with higher capacities have higher price tags.

How many sq ft does a 15000 BTU AC cool?

Those in the 12,000- to 15,000-Btu range cost from $450 to $600, while large units go up to $1,200. Air conditioners rated at 15,000 Btu should be enough to cool most rooms up to about 875 sq. ft.

How much space can a 14 000 BTU air conditioner cool?

Medium rooms: For rooms between 350 and 700 square feet, you’ll want a 11,000-to-14,000 BTU unit. This 12,000-BTU SereneLife air conditioner says it cools rooms up to 450 square feet. Large rooms: Residential units generally top out around 14,000 BTU, enough for 700 square feet at most.

How many square feet will a 9000 BTU AC cool?

400 square feet Area To Be Cooled Capacity Needed (BTUs Per Hour) 300 to 350 square feet 8,000 BTUs 350 to 400 square feet 9,000 BTUs 400 to 450 square feet 10,000 BTUs 450 to 550 square feet 12,000 BTUs.

Does a 6000 BTU air conditioner cool?

In general, a 5,000 to 6,000 BTU air conditioner can cool between 100 and 300 square feet. Seven thousand to 8,200 BTU units are adequate for cooling 250 to 550 square feet, while 9,800 to 12,500 BTU models cool up to 950 square feet.

How is cooling capacity of AC calculated?

To estimate your AC tonnage needs, multiply the number of square feet you’re cooling times 25. This equals the total number of BTUs you need to adequately cool your space. Next, divide that number by 12,000 to determine the tonnage capability you need in your new air conditioning unit.

What size AC do I need for 2000 square feet?

Step 5: Match your square footage to an HVAC size chart Home Sq Footage Air Conditioner Size (tons) 600 – 1,000 square feet 1.5 tons 1,000 – 1,500 square feet 2 tons 1,500 – 2,000 square feet 3 tons 2,000 – 2,500 square feet 4 tons.

What size air conditioner do I need for a 2400 square foot home?

The answer to the question, “what size AC unit for 2400 square feet?”, would be, is 60,000 BTUs or 5 Tons. It’s possible to fall between unit sizes, so if that’s the case with you, then you should choose the next higher size. That way, you can be sure that the AC unit can still cool a given area sufficiently.

How many square feet can a 3 ton unit cool?

3-ton is equal to 36,000 BTU. If you apply the 20 BTU per sq ft rule of thumb, you can see that a 3-ton air conditioner cools about 1,800 square feet spaces.

Is 8000 BTU enough for a bedroom?

Recommended BTU By Room Size If you are looking for an air conditioner for a room measuring say 10′ x 15′ (150 square feet), the recommended BTU range is up to 5400. Once you get into 340 and 400 square feet per room, you’d need an 8,000 or 9,000 BTU air conditioner, respectively.

What size room will a 10000 BTU air conditioner cool?

10,000 BTUs will cover 300 sq. ft. (2,400 cubic feet) 12,000 BTUs will cover 400 sq.

What is the difference between a 14 SEER and a 16 SEER?

The higher the SEER rating, the more efficient your system should be. A 16 SEER unit is about 13% more efficient than a 14 SEER. For every $100 you spend to cool your home with a 14 SEER, you could save $13 on your monthly bill by upgrading to the 16 SEER unit.

Is higher BTU better for air conditioner?

A measure of an air conditioner’s power is its BTU rating. BTUs are the energy used to remove heat from a room. Therefore, the more BTUs an air conditioner unit has, the better equipped it is to cool a larger space.

Is 1 ton AC enough for what room size?

Room size and power consumption Here tonnage plays an important role. For instance, a 1-ton window AC or a 1.5 ton split AC is an ideal choice for rooms measuring up to 150-160 sq ft. Star rating of AC essentially refers to how efficient the air conditioner is in converting electricity to cool air.

How many square feet will a 80000 BTU furnace heat?

How Many Square Feet Will 30,000 – 120,000 BTU Furnace Heat? Furnace Capacity Square Footage(Hot Climate) Square Footage(Cold Climate) 80,000 BTU 2,650 sq ft 1,450 sq ft 90,000 BTU 3,000 sq ft 1,630 sq ft 100,000 BTU 3,320 sq ft 1,810 sq ft 120,000 BTU 4,000 sq ft 2,180 sq ft.